Wall Mounted Air Filtration Systems
The wall mounted air filtration systems are available in two sizes, 350m2 per hour or 850m2 per hour. Ideally, they should be sized to ensure at least 10 to 20 air changes of air per hour are achieved.
In order to give a positive pressure into an environment, they need to be mounted on the wall of a room adjacent to the room requiring clean air. They will then pump air from the adjacent room before cleaning it through the HEPA filter to ensure a clean positive pressure environment.
In order to create a negative pressure in an environment, they need to be mounted inside the room requiring to be kept under negative pressure. The air is then sucked from this room, filtered through HEPA or Carbon filters and then expelled through the outlet of the system to another room or the outside.
For each case, the caplus air cleaner requires a 210mm diameter duct hole in the wall to allow the air to flow between the rooms.
|